Carrier · Heat pump troubleshooting

24K/36K/48K electrical parts and main control board removal

D5FSCAH / D5FLCAH

What is going on

Procedure to remove the electronic control box subassembly and the main control board. Anti-static gloves must be worn for this work.

Check in this order

  1. Wear anti-static gloves.
  2. Remove the 3 screws of the electronic control box and the 1 screw of the earth wire.
  3. Disconnect the connectors of the temperature sensor, pump, motor and water level switch.
  4. Remove the electronic control box subassembly.
  5. Remove the 2 screws of the main control board and the 2 screws of the earth wire.
  6. Disconnect the connectors, then remove the main control board.

Applies to: 24K, 36K and 48K indoor units

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: D5FSCAH / D5FLCAH service manual, p. 69. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.