Daikin · Heat pump troubleshooting
Wiring the thermostat to a communicating indoor unit and outdoor unit
What is going on
Use 18-gauge wire, keep the run under 125 feet, and confirm voltage before and after wiring. The communication bus should read 0.6 VDC between Data 1 and Data 2. Wrong wiring causes a communication error or the equipment will not be recognized.
Likely causes
- Wire run longer than 125 feet
- Thermostat terminals 1, 2, C and R wired to the wrong indoor terminals
- Indoor wires 1 and 2 not matched to outdoor 1 and 2
Check in this order
- Check voltage before wiring.
- Run 18-gauge wire, no longer than 125 feet, between the thermostat and the indoor unit.
- Connect thermostat 1, 2, C and R to indoor unit 1, 2, C and R.
- Connect indoor unit wires 1 and 2 to outdoor unit 1 and 2.
- Check for 0.6 VDC between Data 1 and Data 2.
- Check voltage again after wiring is complete.
Applies to: Communicating indoor and outdoor systems
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin One Touch installation guide, p. 14. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.