Additional R410A refrigerant charge
What is going on
Only R410A is charged during initial installation. Charge after field wiring, the leak test and vacuum drying are complete. Charge liquid only, because R410A is a blend. Overcharging can damage the compressor.
Check in this order
- Confirm the airtight test and vacuum drying are complete.
- Calculate the additional charge using the formula in the setting table for this manual.
- Open valve B only. Keep valve A and the liquid/gas stop valve closed. Charge from the liquid stop valve service port.
- Close valve B after the calculated amount is charged.
- If the full amount does not fit, open valve A only (stop valves closed) and charge the rest.
- Close the cylinder valve right after charging. Leaving it open can overcharge the system.
- Write the added amount on the additional refrigerant label and attach it to the back of the front panel.
- Check whether the cylinder has a siphon tube. Charge liquid with the cylinder upright, or upside down only if it has no siphon tube, so the refrigerant enters as liquid.
Applies to: Heat source unit with cascade unit R410A liquid piping
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Mega-Q installation manual, p. 35-36. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.