Brazing refrigerant piping with nitrogen
What is going on
Braze with nitrogen flowing through the pipe so oxide scale does not form inside the lines. Without it, scale can clog or damage valves and compressors.
Check in this order
- Replace the air with nitrogen and keep nitrogen flowing while brazing.
- Use a pressure reducing valve on the nitrogen supply. Set it to about 3 psi (0.02 MPa).
- Protect the area around the joint with tape or a pad.
- Do not use antioxidant paste when brazing; residue can clog piping and damage parts.
Applies to: Heat source unit and cascade unit refrigerant piping
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin Mega-Q installation manual, p. 16. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.