Auxiliary output wiring

Daikin One Touch

What is going on

The thermostat Aux outputs are dry contacts that close to switch on an auxiliary device. A 24VAC control signal must be routed through one of the Aux contacts. Aux terminals are chosen in the Daikin One installer wizard. Use a minimum of 18-gauge wire and keep the run under 125 feet.

Check in this order

  1. Wire the auxiliary device through an Aux 1 or Aux 2 dry contact (N.O. and Com).
  2. Route the 24VAC control signal through one of the Aux contacts.
  3. Use at least 18-gauge wire, no longer than 125 feet.
  4. Select the Aux terminal in the Daikin One installer wizard.
  5. Confirm the field device has its own line voltage supply through the relay.

Applies to: Auxiliary equipment on the One Touch thermostat

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin One Touch installation guide, p. 16. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.