Gree · Heat pump troubleshooting
Weak cooling or heating - Gree ductless
What is going on
The mini split runs but the room never gets to temperature. Gree Sapphire, Livo, Vireo and Multi21+. Most of this comes from the simple end of the list, then installation, then refrigerant.
Likely causes
- Setpoint or fan speed too low
- Dirty filter
- Poor indoor or outdoor unit location
- Refrigerant leak
- 4-way valve fault, giving cold air in heating
- Capillary or EEV restriction
- Service valve not fully open
Check in this order
- Check setpoint and set fan to high or medium, because low fan speed cuts delivered capacity
- Clean the filter, a clogged filter chokes airflow
- Check installation clearances and shading of the outdoor unit, blocked air starves the coil
- Compare supply air temperature and pressures with normal, low readings point to a leak or restriction
- Open both service valves fully, a half-open valve acts like a restriction
- Cold air in heating with good charge replace the 4-way valve
- Refrigerant work needs a licensed technician
Applies to: Gree Sapphire 9-24k (SAP..HP230V1A), Livo GEN4 30-36k (4LIV..HP230V1A), Vireo GEN3 9-24k (3VIR..HP115/230V1A), Multi21+ 18-24k multi-zone (MULTI..HP230V1CO)
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Gree Sapphire 9-12k (SAP09-12HP230V1A) service.pdf - section 9.3 Troubleshooting for Normal Malfunction; Gree Sapphire 18-24k (SAP18-24HP230V1A) service.pdf - section 9.3 Troubleshooting for Normal Malfunction; Gree Livo GEN4 30-36k (4LIV30-36HP230V1A) service.pdf - section 9.3 Troubleshooting for Normal Malfunction; Gree Vireo GEN3 9-24k (3VIR..HP115-230V1A) service GREE_VIREOGEN3_SERVICE_090921.pdf - section 9.3 Troubleshooting for Normal Malfunction; Gree Multi21+ multi-zone 18-24k (MULTI18-24HP230V1CO) service.pdf - section 9.3 Maintenance Method for Normal Malfunction. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.