Daikin · Heat pump troubleshooting

Using emergency mode when communication or thermostat fails

DX6VS / DZ6VSDV**FEC / DFVE**CAPE(A)* / CHPE*

What is going on

Emergency mode is a temporary measure only, for when wiring or a thermostat fault cannot be fixed right away. Once repairs are made, emergency mode must be turned off and the system returned to normal operation on both indoor and outdoor units. Emergency mode does not hold a set room temperature.

Likely causes

  • Broken communication wiring
  • Failed thermostat

Check in this order

  1. Turn off power to all equipment before changing wiring or DIP switches.
  2. Use only the emergency mode steps for the specific unit (heating or cooling).
  3. After repairs, reset all emergency DIP switches to factory default and restore the thermostat wiring.

Applies to: EEV indoor units and outdoor units when communication or thermostat fails

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin SiUS612209EB service instructions, p. 32-34. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.