Daikin · Heat pump troubleshooting
Unspecified voltage / wrong pair-multi combination, code UA
What is going on
The indoor/outdoor transmission signal shows a pair-type unit connected to a multi-type unit, meaning the wrong models are interconnected.
Likely causes
- Wrong models interconnected
- Wrong wiring of connecting wires
- Wrong indoor unit PCB or outdoor unit PCB fitted
- Defective indoor unit PCB
- Defective outdoor unit PCB
Check in this order
- Turn off the power switch before connecting or disconnecting any connector.
- Check that the indoor and outdoor models are compatible.
- If they are not compatible, correct the combination.
- Check the code numbers of the indoor and outdoor PCBs (example format 2P012345) against the Parts List.
- If a PCB does not match, replace it with the correct PCB.
- Check that the connecting wires are connected properly, and correct any wiring error.
- Recheck the indoor and outdoor combination.
Applies to: Inverter pair wall mounted FTXM-W/V
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin FTXM-W/V service manual SiUS042113EA, p. 115. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.