Daikin · Heat pump troubleshooting

Unit runs but does not cool or heat

FTXM-W/V

What is going on

System runs but gives no useful heating or cooling effect.

Likely causes

  • Wiring or piping errors between indoor and outdoor units
  • Faulty thermistor or loose thermistor mounting
  • Electronic expansion valve not working
  • Refrigerant shortage

Check in this order

  1. Check wiring and piping between indoor and outdoor units for errors.
  2. Check that each thermistor is mounted securely.
  3. Set the unit to cooling and check the liquid pipe temperature to confirm the electronic expansion valve is working.
  4. Read the error code on the remote controller (p. 96).
  5. Check service port pressure and operating current to look for refrigerant shortage.

Applies to: FTXM-W/V wall mounted indoor and outdoor units

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin FTXM-W/V service manual SiUS042113EA, p. 96. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.