Unit operates but does not cool or does not heat
What is going on
The unit runs but gives no cooling or heating. Check wiring and piping, sensors, the expansion valve and refrigerant charge.
Likely causes
- Wiring or piping errors between indoor and outdoor units
- Thermistor detection error or loose thermistor
- Faulty electronic expansion valve operation
- Refrigerant shortage
Check in this order
- Check the wiring and piping between the indoor and outdoor units for errors.
- Check that each thermistor is mounted securely.
- Set the unit to cooling and check the liquid pipe temperature to see whether the electronic expansion valve works.
- Diagnose using the remote controller indication (see p. 96).
- Check service port pressure and operating current to look for refrigerant shortage.
Applies to: FTXM-W/V wall mounted inverter pair
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SiUS042113EA service manual, p. 96. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.