Three-step nitrogen system pressure test
What is going on
Recommended pressure test once all refrigerant line connections are complete. Each step holds pressure to check for drops. Any drop means finding and repairing the leak, then repeating from step 1.
Check in this order
- Pressurise with nitrogen to 150 PSIG and hold for 3 minutes.
- Pressurise with nitrogen to 325 PSIG and hold for 5 minutes.
- Pressurise with nitrogen to 450 PSIG and hold for 4 hours.
- If any pressure drop occurs at any step, locate and repair the leak and repeat from step 1.
Applies to: DX6VS / DZ6VS / DZ6VSA outdoor units
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin DX6VS/DZ6VS installation manual (3P731493-1), p. 17. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.