Testing thermistors
What is going on
Factory sensors on outdoor units and EEV indoor units are: Ta (outdoor air), Tm (outdoor coil), Tl (outdoor liquid), Td (discharge), Tb (coil defrost), Ts (suction), Tgi (indoor gas) and Tli (indoor liquid). Compare readings against the resistance table in the manual.
Likely causes
- Open thermistor
- Shorted thermistor
- Resistance outside valid range
Check in this order
- Disconnect power to all equipment.
- Unplug the thermistor connector from the control board.
- Connect an ohmmeter across the thermistor terminals.
- Compare the reading with the thermistor resistance and temperature table.
- Replace the thermistor if it is open, shorted, or outside the valid resistance range.
Applies to: Outdoor unit and EEV indoor unit thermistors
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 21. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.