Test inverter capacitor DC voltage before servicing

DX6VSDZ6VS

What is going on

Check the DC voltage on the inverter capacitor before touching the control board or wiring. Discharge first, then confirm the voltage is low.

Check in this order

  1. Turn off power and wait at least 10 minutes for the capacitor to discharge.
  2. Set the multimeter to DC voltage range.
  3. Measure across the capacitor terminals C+ and C-.
  4. Confirm the reading is 50 V DC or less before working on the board.
  5. Do not work on the capacitor or board if the reading is above 50 V DC. Discharge it first.

Applies to: 1.5 - 5.0 ton outdoor units (1.5-3.0 ton and 3.5-5.0 ton diagrams)

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EA, p. 5-6. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.