Carrier · Heat pump troubleshooting

Test DC voltage between communication ports and reactor resistance

D5FCFA

What is going on

Used to tell a normal communication signal from a fault on the outdoor or indoor side.

Check in this order

  1. Set the multimeter to DC voltage.
  2. Connect the red lead to the 2 port (or S or L2 port) and the black lead to the 3 port (or N or S port) of the outdoor unit.
  3. With the AC running normally, the voltage swings between positive and negative values.
  4. If the voltage is always positive, suspect the outdoor unit.
  5. If the voltage stays at one fixed value, suspect the indoor unit.
  6. To check the reactor, disconnect it from the capacitor and measure its resistance. A normal reading is close to zero ohms. Replace the reactor if it is not.

Applies to: Outdoor unit communication circuit

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: D5FCFAH service manual, p. 36. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.