Daikin · Heat pump troubleshooting

Signal transmission error code U4

FTXM-WFTXM-V

What is going on

Indoor and outdoor units are not receiving valid signal data from each other.

Likely causes

  • Power supply voltage out of specification
  • Voltage drop on the supply
  • Wiring error between indoor and outdoor units
  • Broken indoor-outdoor connection wire (wire No. 3)
  • Defective outdoor unit PCB
  • Short circuit in the fan motor winding
  • Defective indoor unit PCB
  • Disturbed power supply waveform

Check in this order

  1. Turn off the power switch before connecting or disconnecting any connector.
  2. Check the power supply waveform for disturbance. Refer to Check No. 11 (P.142).
  3. Measure the voltage on the indoor terminal board between No. 1 and No. 3, and between No. 2 and No. 3.
  4. Check LED A on the outdoor unit PCB. If it blinks, continue to the wiring checks. If it stays continuously on or off, follow the fault path for the outdoor PCB.
  5. Check the indoor-outdoor connection wires for wiring errors, insulation and damage.
  6. Correct any wiring error found.
  7. Replace the connection wires if they are damaged or broken.
  8. If there is power supply disturbance, locate its cause and correct it.
  9. If the indoor terminal voltage is wrong, replace the indoor unit PCB (control PCB).
  10. If the outdoor PCB shows the fault, replace the outdoor unit PCB (main PCB).
  11. Check the supply voltage and correct it if out of range.
  12. Rotate the outdoor fan by hand. If it does not turn smoothly, or voltage fluctuation is outside ±10%, replace the outdoor fan motor and outdoor unit PCB.

Applies to: Inverter pair wall mounted FTXM-W/V, indoor to outdoor communication

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin FTXM-W/V service manual SiUS042113EA, p. 113. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.