Carrier · Heat pump troubleshooting

Scenario 1: 24V thermostat with RS485 communication wiring

D5CURA

What is going on

Preferred method. Lets a 24V thermostat work with RS485 communication between the indoor and outdoor units. No 24V terminal at the outdoor unit can be used in this scenario.

Check in this order

  1. Use 16 AWG stranded shielded cable for RS485 between indoor and outdoor units.
  2. Do not use the B terminal and W terminal together at the air handler.
  3. Use W only with a conventional thermostat for the heat demand at the air handler.
  4. Leave DS unused; it is a reserve terminal.
  5. Set the indoor unit dip switches for Scenario 1 as shown in the manual (Fig. 11).
  6. Never connect 24V AC to S1 - S2; this damages the system.

Applies to: D5CURA with 24V thermostat and compatible indoor unit

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: D5CURA product data, p. 117. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.