Daikin · Heat pump troubleshooting

S-4 Checking transformer and control circuit

DX6VS / DZ6VS

What is going on

The indoor unit has a step-down transformer (208/230 or 115 V primary to 24 V secondary). The outdoor unit has no transformer.

Likely causes

  • No secondary voltage: faulty transformer, bad wiring or bad splices
  • Line voltage missing at the primary

Check in this order

  1. Disconnect all power before servicing.
  2. Remove the control panel cover to access the transformer.
  3. With power on, use a voltmeter to check voltage across the transformer secondary (R to C).
  4. If there is no voltage, check the transformer primary voltage at the incoming line voltage connections or splices.
  5. If line voltage is present at the primary and the wiring and splices are good, replace the transformer.

Applies to: Indoor unit transformer, EEV air handler

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin DX6VS / DZ6VS service instructions SiUS612209EA, p. 16. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.