Daikin · Heat pump troubleshooting
S-3E Daikin communicating thermostat wiring
What is going on
The system uses data lines and 24 VAC power between indoor unit, outdoor unit and thermostat.
Likely causes
- Wiring errors between the indoor unit, outdoor unit and thermostat
- Poor communication reliability from loose or unshielded field wiring
Check in this order
- Run two wires between the indoor unit and the outdoor unit for data lines 1 and 2.
- Run four wires between the indoor unit and the communicating thermostat: data lines 1 and 2, R (24 VAC hot) and C (24 VAC common).
- Use the same wire type and gauge as the factory wiring; 18 AWG is recommended.
- Consider a high quality shielded, twisted pair cable for data lines to improve communication reliability.
- Confirm all wires are secure at each terminal.
Applies to: EEV air handler and EEV cased coil with Daikin One+ communicating thermostat
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin DX6VS / DZ6VS service instructions SiUS612209EA, p. 15. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.