Daikin · Heat pump troubleshooting

S-12 Checking high pressure switch

DX6VS / DZ6VS

What is going on

The high pressure switch senses compressor discharge pressure and opens the control circuit on abnormally high condensing pressure. It does not reset automatically.

Likely causes

  • Open switch contacts from high condensing pressure
  • Open circuit in switch wiring

Check in this order

  1. Disconnect all power before servicing.
  2. With wire on the PCB side removed, use an ohmmeter across the PCB side terminals of the high pressure switch.
  3. If the reading is not continuous, the circuit is open; replace the switch if necessary.
  4. After the cause is fixed, turn main power off to reset the switch.

Applies to: DX6VS / DZ6VS outdoor unit high pressure switch

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin DX6VS / DZ6VS service instructions SiUS612209EA, p. 16. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.