Daikin · Heat pump troubleshooting

S-1 Checking voltage

DX6VS / DZ6VS

What is going on

Check supply voltage before servicing the control circuit or components.

Likely causes

  • No reading at line voltage: open wiring, open fuse, no power, or a fault from the unit to the fused disconnect.

Check in this order

  1. Remove the outer case and control panel cover from the unit being tested.
  2. With power on, use a voltmeter to measure across L1 and L2 at the outdoor unit, or at the field connections for indoor units or heaters.
  3. If there is no reading, repair the open wiring, fuse, or supply as needed.
  4. With ample voltage at the line voltage connectors, energize the unit.
  5. Compare readings with the supply voltage limits table.

Applies to: DX6VS / DZ6VS outdoor units and indoor units

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin DX6VS / DZ6VS service instructions SiUS612209EA, p. 15. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.