RS485 communication error between indoor and outdoor unit

D5FCFA

What is going on

The indoor unit cannot communicate with the outdoor unit over the RS485 line. No specific code is shown on these pages.

Likely causes

  • Interference from nearby lamps, power transformers, or a long signal wire
  • Signal wire not shielded or shield not earthed
  • Broken signal wire
  • Signal wires not seated properly on the PCB
  • Faulty indoor or outdoor main PCB

Check in this order

  1. Turn the power off, then restart the unit 2 minutes later.
  2. Check whether the signal wire is shielded and whether the shield is earthed. Use shielded cable with the shield earthed.
  3. Check for interference such as many lamps or power transformers, or a signal wire that is too long. Remove the interference or add a magnetic ring on the power wire.
  4. Check that the signal wire is not broken and replace it if it is.
  5. Check that the signal wires are fully seated on the PCB. Pull them out and reinsert them.
  6. Replace the indoor main PCB and check whether the error clears.
  7. If the error remains, replace the outdoor main PCB.

Applies to: Indoor and outdoor unit RS485 communication

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: D5FCFAH service manual, p. 35. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.