Carrier · Heat pump troubleshooting
Routing the connecting pipe between units
What is going on
Keep the refrigerant line within limits and stop water getting into the indoor unit.
Likely causes
- Rain running down the line can enter the indoor unit.
- Buried pipe that is too long lets refrigerant migrate, causing slugging at start-up.
Check in this order
- Check the height difference and total length against Table 6.
- If the outdoor unit is higher than the indoor unit, make a downward arc in the pipe before it enters the wall so rain drips off first.
- Do not bury more than 36 in (914 mm) of refrigerant pipe. If any is buried, give it a 6 in (152 mm) vertical rise to the outdoor valve connections.
- Do not install the connecting pipe until both the indoor and outdoor units are in place.
Applies to: Field refrigerant piping
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Carrier D5CURA installation manual, p. 8 and p. 13. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.