Carrier · Heat pump troubleshooting

Routing the connecting pipe between units

D5CURA

What is going on

Keep the refrigerant line within limits and stop water getting into the indoor unit.

Likely causes

  • Rain running down the line can enter the indoor unit.
  • Buried pipe that is too long lets refrigerant migrate, causing slugging at start-up.

Check in this order

  1. Check the height difference and total length against Table 6.
  2. If the outdoor unit is higher than the indoor unit, make a downward arc in the pipe before it enters the wall so rain drips off first.
  3. Do not bury more than 36 in (914 mm) of refrigerant pipe. If any is buried, give it a 6 in (152 mm) vertical rise to the outdoor valve connections.
  4. Do not install the connecting pipe until both the indoor and outdoor units are in place.

Applies to: Field refrigerant piping

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Carrier D5CURA installation manual, p. 8 and p. 13. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.