Daikin · Heat pump troubleshooting
Reviewing D-Checker data for system health
What is going on
Check the logged values against the expected ranges below. A protection showing as active does not by itself mean a fault. Read it with the other data and the unit's IO manual.
Likely causes
- Discharge temperature mismatch can point to overcharge or undercharge.
- Heat exchanger temperatures that do not match the operating mode can point to a flow or charge problem.
- Expansion valve pulses outside range can point to a valve or charge issue.
Check in this order
- Compare the target discharge temperature with the actual discharge temperature. Allow about 20 minutes for the software to calculate the target.
- If the target is higher than the actual, the manual says this may indicate an overcharge.
- If the actual is higher than the target, the manual says this may indicate an undercharged system.
- Check the protection values. 255 means the protection is inactive.
- Check heat exchanger temperatures against the cooling or heating range shown in the expansion valve and voltage reference table.
- Check that the expansion valve is operating at 25 to 50 percent of its range, with a maximum of 480 pulses.
- Check that supply voltage is between 187 and 253 VAC.
Applies to: DX6VS / DZ6VS inverter outdoor units
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin SiUS612209EA service instructions, p. 134. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.