Reviewing D-Checker data for system health

DX6VSDZ6VS

What is going on

Check the logged values against the expected ranges below. A protection showing as active does not by itself mean a fault. Read it with the other data and the unit's IO manual.

Likely causes

  • Discharge temperature mismatch can point to overcharge or undercharge.
  • Heat exchanger temperatures that do not match the operating mode can point to a flow or charge problem.
  • Expansion valve pulses outside range can point to a valve or charge issue.

Check in this order

  1. Compare the target discharge temperature with the actual discharge temperature. Allow about 20 minutes for the software to calculate the target.
  2. If the target is higher than the actual, the manual says this may indicate an overcharge.
  3. If the actual is higher than the target, the manual says this may indicate an undercharged system.
  4. Check the protection values. 255 means the protection is inactive.
  5. Check heat exchanger temperatures against the cooling or heating range shown in the expansion valve and voltage reference table.
  6. Check that the expansion valve is operating at 25 to 50 percent of its range, with a maximum of 480 pulses.
  7. Check that supply voltage is between 187 and 253 VAC.

Applies to: DX6VS / DZ6VS inverter outdoor units

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin SiUS612209EA service instructions, p. 134. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.