Reversing valve, solenoid valve and EEV coil removal (3.5 to 5.0 ton HP)

DX6VSDZ6VS

What is going on

Removal of the valve coils on the heat pump refrigerant circuit. Torque values are given in the setting table for this section.

Check in this order

  1. Cut the 2 clamps on the solenoid valve coil lead wire.
  2. Remove 2 screws and take off the solenoid valve coil.
  3. Remove 1 screw and take off the four way valve coil.
  4. Cut the clamp and pull out the electronic expansion valve (EEV) coil.
  5. Tighten the coils to the torque values in the torque table when reassembling.

Applies to: 3.5 to 5.0 ton HP outdoor units

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 112. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.