Daikin · Heat pump troubleshooting

Removing pinch piping from the heat source unit

Mega-Q

What is going on

Pinch piping must be vented before it is removed, otherwise the stop valve can rupture or residual oil can catch fire.

Check in this order

  1. Remove the valve cover and check that the stop valve is fully closed.
  2. Connect a charge hose with push rod to the service port and check for no residual pressure.
  3. Cut the small pinch piping with a piping cutter so a cross section opens. Confirm again there is no residual pressure.
  4. Leave the pipe until the oil runs out.
  5. Remove the large pinch piping.
  6. Drain all gas and oil from the pinch piping before removing it.

Applies to: Heat source unit stop valve connections

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin Mega-Q installation manual, p. 18. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.