Remove thermistors and insulation tube on HP models
What is going on
HP 1.5 to 3.0 ton units. Remove the outdoor air, outdoor coil and defrost thermistors, then the suction, discharge and liquid pipe thermistors. Detach the overload (OL) relay and HPS connectors. The insulation tube is cut free for the suction thermistor.
Check in this order
- Remove the outdoor air thermistor and the outdoor coil thermistor.
- Remove the defrost thermistor. On 1.5/2.0/2.5 ton and 3.0 ton units the coil and defrost thermistors are in different positions, so check the diagram.
- Remove the suction pipe, discharge pipe and liquid pipe thermistors.
- Detach the OL relay connector and the HPS connectors.
- Cut the 2 clamps and remove the insulation tube from the suction pipe thermistor.
- When reassembling, face the slit in the insulation tube away from the suction pipe thermistor.
- When reassembling, keep the lead wires from touching the edges.
- The HPS sits inside the sound blanket (outer body).
Applies to: 1.5 to 3.0 ton HP models
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin sm-sius612209ea service instructions, pp. 89-90. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.