Daikin · Heat pump troubleshooting

Remove the top, front panel and discharge grille (1.5 to 3.0 ton)

DX6VS / DZ6VS inverter outdoor units

What is going on

Access steps after the side panel is removed. The front panel hook must sit in the partition plate slit on reassembly.

Check in this order

  1. Remove the 4 screws and lift off the top panel.
  2. Remove the 5 screws and remove the front panel. The circled screw is a truss head tapping or hex head screw.
  3. On reassembly, insert the front panel hook into the slit of the partition plate.
  4. Remove the 4 screws and remove the discharge grille.

Applies to: 1.5 to 3.0 ton HP and AC outdoor units

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin SiUS612209EB service instructions, p. 81-82. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.