Daikin · Heat pump troubleshooting

Remove the solenoid valve, four way valve and EEV coils

DX6VS / DZ6VS

What is going on

Removal of the coil leads from the valves on 3.5 to 5.0 ton HP models.

Check in this order

  1. Cut the 2 clamps on the solenoid valve coil lead wire.
  2. Remove the 2 M4 screws and take off the solenoid valve coil.
  3. Remove the 1 M5 screw and take off the four way valve coil.
  4. Cut the clamp and pull out the electronic expansion valve coil.
  5. On reassembly, torque the solenoid coil screws to 1.47-1.96 N·m and the four way coil screw to 3.2±0.8 N·m.

Applies to: 3.5 to 5.0 ton HP models

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin SiUS612209EA service instructions, p. 112. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.