Daikin · Heat pump troubleshooting
Remove the outdoor fan and fan motor (3.5 to 5.0 ton)
What is going on
Disconnect the fan motor, remove the fan nut and fan, then remove the motor stand and motor.
Check in this order
- Disconnect the fan motor connector (X108A) and release the lead wire from the hooks.
- Remove the M8 nut and take off the fan.
- Remove 2 screws and take off the fan motor stand.
- Remove 4 screws and take off the fan motor. These are 3 class hex head tapping screws (M5 × 25).
Applies to: 3.5 to 5.0 ton HP & AC
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin SiUS612209EA service instructions, pp. 109-110. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.