Daikin · Heat pump troubleshooting

Remove the fan motor and fan (1.5 to 3.0 ton)

DX6VS / DZ6VS inverter outdoor units

What is going on

Fan removal sequence. Model-specific differences are noted for 1.5/2.0 ton and 2.5/3.0 ton units.

Check in this order

  1. Remove the 1 truss head screw and the drip proof cover. Unhook the fan motor lead from the cover.
  2. Cut the clamp and disconnect the fan motor connector X200A.
  3. Remove the fan nut (M8) and remove the fan.
  4. Remove the 2 screws and remove the fan motor stand.
  5. Remove the 4 hex head tapping screws (M5 x 25) and remove the fan motor.

Applies to: 1.5 to 3.0 ton HP and AC outdoor units

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin SiUS612209EB service instructions, p. 84-86. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.