Daikin · Heat pump troubleshooting
Remove the electrical box and main control board
What is going on
Access the main control board on 3.5 to 5.0 ton units. Some connectors are HP models only.
Check in this order
- Remove the 2 screws and the refrigerant cooling pipe jacket cover.
- Remove the 2 screws and the electrical box. Detach the HPS connectors.
- Disconnect all connectors on the main control board: EEV coil (X21A), thermistors (X12A), HPS (X32A), four way valve coil (X25A, HP only), solenoid valve coil (X28A, HP only), power supply (L1, L2), OL (X33A) and ground (E1, E3).
- Remove the 11 screws, then remove the main control board and insulation sheet.
- Torque the jacket cover screws and apply grease as specified on reassembly.
Applies to: 3.5 to 5.0 ton HP and AC models
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin SiUS612209EA service instructions, p. 116, 117. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.