Daikin · Heat pump troubleshooting

Remove sound blankets, disconnect compressor leads and remove the compressor (HP models)

DX6VS / DZ6VS

What is going on

Compressor removal on 3.5 to 5.0 ton HP models. Wiring and the brazed joints differ by model size.

Check in this order

  1. Remove the 6 M5 x 16 screws and the stop valve mounting plate. Remove the conduit tube if connected.
  2. Remove the top sound blanket and then the body sound blanket.
  3. Remove the terminal cover.
  4. Disconnect the compressor lead wires. U is red, V is yellow and W is blue. Wiring differs between 3.5/4.0 ton and 5.0 ton, so reconnect exactly as shown.
  5. Remove the OL. On reassembly, insert the lower retainer hooks into the fixture square holes, then push the upper hooks until they latch. Pass the OL lead wire through the harness.
  6. Before brazing, remove putty, the terminal cover and any plastic parts that could burn. Protect the surroundings with a sheet or steel plate.
  7. Heat the brazed joints of the compressor piping and disconnect them, keeping the piping within the allowed slit range.
  8. Remove the 2 nuts that secure the compressor.

Applies to: 3.5 to 5.0 ton HP models

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin SiUS612209EA service instructions, p. 118, 119, 120. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.