Daikin · Heat pump troubleshooting
Remove partition plate and sound blankets on HP models
What is going on
HP 1.5 to 3.0 ton units. Remove the partition plate and the outer top sound blanket. When reassembling, the outer top blanket must sit inside the outer body blanket and must not rise above it.
Check in this order
- Remove 2 screws (the upper one is a truss head tapping or hex head M4 x 12) and remove the partition plate.
- When reassembling, insert the hook of the bottom frame into the slit of the partition plate.
- Remove the sound blanket (outer top).
- When reassembling, insert the full circumference of the outer top blanket inside the outer body blanket.
- Make sure the outer top blanket does not rise above the outer body blanket.
Applies to: 1.5 to 3.0 ton HP models
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin sm-sius612209ea service instructions, p. 96. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.