Daikin · Heat pump troubleshooting
Remove partition plate and outer sound blanket (heat pump, 1.5 to 3.0 ton)
What is going on
Start of the compressor access sequence for heat pump models. The sequence continues on the following pages.
Check in this order
- Remove the 2 screws and take off the partition plate. The upper screw is a truss head tapping screw or hex head screw (M4 x 12). On reassembly, insert the bottom frame hook into the slit of the partition plate.
- Remove the sound blanket (outer top).
- On reassembly, insert all of the outer top blanket edge into the outer body blanket. Make sure the outer top blanket does not stand above the outer body blanket.
Applies to: DX6VS / DZ6VS heat pump outdoor units, 1.5 to 3.0 ton
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 96. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.