Daikin · Heat pump troubleshooting
Remove panels, grille and rear plate (1.5 to 3.0 ton outdoor units)
What is going on
Panel and cover removal for 1.5 to 3.0 ton heat pump and AC outdoor units. Reassemble in reverse order.
Check in this order
- Remove the 8 screws and take off the right side panel.
- Remove the 4 screws and take off the top panel.
- Remove the 5 screws and take off the front panel. When reassembling, hook the front panel into the slit of the partition plate.
- Remove the 4 screws and take off the discharge grille.
- Cut the 2 clamps, then remove the 3 terminal block screws (1 M5 x 12 and 2 M4 x 10). Disconnect the external power, ground and communication wires from the terminal block.
- Remove the 7 screws and take off the rear plate.
Applies to: 1.5 to 3.0 ton HP and AC outdoor units
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EA, p. 81-83. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.