Daikin · Heat pump troubleshooting

Remove heat exchanger - heat pump models, 3.5 to 5.0 ton

DX6VSDZ6VS

What is going on

Heat exchanger and partition plate removal on heat pump outdoor units.

Check in this order

  1. Remove the 3 screws holding the rear cover and remove the cover.
  2. Heat the brazed joints of the heat exchanger and disconnect them. Protect nearby plastic and putty as noted in the manual.
  3. Remove the 3 screws holding the heat exchanger and lift it out.
  4. Remove the partition plate. On 4-screw models remove 4 screws; on 3-screw models remove 3 screws.
  5. On reassembly, insert the hook on the bottom frame into the slit in the partition plate.

Applies to: 3.5 to 5.0 ton heat pump outdoor units

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 124-125. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.