Daikin · Heat pump troubleshooting

Remove heat exchanger, heat pump 3.5 to 5.0 ton

DX6VSDZ6VS

What is going on

Heat pump models only. The heat exchanger is removed after the rear cover and brazed joints, then the partition plate.

Check in this order

  1. Remove the 3 screws and take off the rear cover.
  2. Protect nearby putty, terminal cover and plastic parts from the brazing flame, and shield with a steel plate or protective sheet.
  3. Heat the brazed heat exchanger joints and disconnect them. The 5.0 ton model is shown as the representative drawing.
  4. Remove the 3 screws and take off the heat exchanger.
  5. On a 4 screw model, remove the 4 screws and the partition plate. On a 3 screw model, remove the 3 screws and the partition plate.
  6. When reassembling the partition plate, insert the hook of the bottom frame into the slit of the partition plate.

Applies to: DX6VS / DZ6VS heat pump outdoor units, 3.5 to 5.0 ton

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EA, pp. 124 to 125. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.