Remove front right panel, front panel, water collecting cover, rear net and right panel (18K to 36K outdoor unit)

D5CURA

What is going on

Panel removal sequence for the outdoor unit. The pages start partway through the procedure, so steps 1 to 3 are not included here. Do not assume the unit size from this section alone; check the manual's disassembly pages for the size the procedure applies to.

Check in this order

  1. Remove the screws of the front right panel, then remove the front right panel (2 screws).
  2. Remove the screws of the front panel, then remove the front panel (9 screws).
  3. Remove the screws of the water collecting cover, then remove the water collecting cover (2 screws).
  4. For some models, remove the screws of the rear net, then remove the rear net (3 screws).
  5. Remove the screws of the right panel, then remove the right panel (8 screws).

Applies to: D5CURA outdoor units, sizes not stated on these pages (steps 1 to 3 missing)

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Carrier D5CURA service manual, p. 72 to 74. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.