Daikin · Heat pump troubleshooting

Remove four way valve, solenoid valve and EEV coils

DZ6VS

What is going on

HP 1.5 to 3.0 ton units. Remove the coils after the leads are off, then pull out the electronic expansion valve (EEV) coil and remove the compressor lead.

Check in this order

  1. Remove 2 screws and take off the solenoid valve coil.
  2. Remove 1 screw and take off the four way valve coil.
  3. Pull out the electronic expansion valve coil.
  4. Remove the 3 clamps and disconnect the compressor lead wire at the U, V, W connector.
  5. Tighten the four way valve coil to the torque in the torque table.
  6. Tighten the solenoid valve coil to the torque in the torque table.

Applies to: 1.5 to 3.0 ton HP models

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin sm-sius612209ea service instructions, p. 89. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.