Daikin · Heat pump troubleshooting

Remove fan, fan motor and fan motor stand (1.5 to 3.0 ton)

DX6VSDZ6VS

What is going on

Fan and fan motor removal for 1.5 to 3.0 ton outdoor units. Route the fan motor lead correctly on reassembly.

Check in this order

  1. Remove the 1 screw and take off the drip proof cover. Unhook the fan motor lead from the drip proof cover hook.
  2. Cut the clamp and disconnect the fan motor connector (X200A).
  3. Remove the M8 nut and take off the fan.
  4. Remove the 2 screws and take off the fan motor stand.
  5. Remove the 4 M5 x 25 hex head tapping screws and take off the fan motor.
  6. On reassembly, bend the 2 claws of the fan motor stand and fix the lead wire.
  7. On reassembly, route the fan motor lead through the hole in the stand (required on 2.5/3.0 ton), keep the lead downward, and leave no slack.
  8. On 1.5/2.0 ton units, clamp the compressor lead wires about 20 to 50 mm from the end of the fan motor lead protective tube and keep them free of tension.

Applies to: 1.5 to 3.0 ton HP and AC outdoor units

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EA, p. 84-87. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.