Daikin · Heat pump troubleshooting
Remove electrical box, stay and main control board
What is going on
1.5 to 3.0 ton HP and AC units. The electrical box hooks onto the tube plate. Remove the climate talk board and the main control board in order, and keep the wire ends stripped and curled correctly.
Check in this order
- Remove 1 screw and lift the electrical box off the tube plate (it hangs on a hook).
- Remove the 2 stay screws (truss head tapping or M4 x 12) and remove the stay.
- Disconnect the wires on the climate talk board (functional module) and remove the board.
- When reassembling, curl the end of each lead and strip the wire only as far as the good-practice mark.
- Disconnect all connectors on the main control board.
- Remove the 3 screws (truss head or M4 x 12) and take off the electrical component box cover.
- Remove the 10 screws in the groups shown and remove the main control board.
- When reassembling, tighten each board screw to the torque in the torque table.
Applies to: 1.5 to 3.0 ton HP and AC models
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin sm-sius612209ea service instructions, pp. 93-95. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.