Remove electric auxiliary heat module (optional)

D5FUAA

What is going on

Removes the optional electric auxiliary heat module and its fuse. Disconnect power and lock out before starting. Quantity of modules per model is listed in the setting table for this section.

Check in this order

  1. Remove the 2 screws from the upper cover plate assembly and remove the plate.
  2. Remove the 3 fixing screws.
  3. Pull out the auxiliary heat module.
  4. Use needle-nose pliers to pull the wire connected to the fuse.
  5. Loosen the retaining nut and remove the fuse.

Applies to: D5FUAA with optional EHKMB auxiliary heat module

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Carrier D5FUAA service manual, p. 50-51. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.