Daikin · Heat pump troubleshooting

Remove compressor - heat pump models, 3.5 to 5.0 ton

DX6VSDZ6VS

What is going on

Removal and reinstall steps for the compressor on heat pump outdoor units. Shown on the step 6-7 pages only; steps 1-5 are not on these pages.

Check in this order

  1. Remove the overload (OL) device. When refitting, hook the lower tabs of the retainer into the square holes of the fixture first, then push the upper hooks until they latch in the square holes. Route the OL lead wire and harness as shown.
  2. Before any brazing, remove putty, the terminal cover and other plastic parts that could burn. Put a protective sheet or steel plate under the work so the flame does not reach nearby parts.
  3. Heat the brazed joints of the compressor piping and disconnect them. Keep the piping strain within the angle shown in the manual.
  4. Remove the 2 nuts that hold the compressor to the base. The nut and brazed-part locations differ between 3.5/4.0 ton and 5.0 ton units.

Applies to: 3.5 to 5.0 ton heat pump outdoor units

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 120. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.