Remove compressor, heat pump 3.5 to 5.0 ton (overload and brazed piping)

DX6VSDZ6VS

What is going on

Heat pump models only. Covers the last steps of compressor removal: overload (OL) and brazed piping. Steps 1 to 5 are on the previous page and are not in this extract.

Check in this order

  1. Remove the OL. When reassembling, fit the retainer first: insert its lower hooks into the square holes of the fixture, then push the upper hooks until they latch in the square holes.
  2. Route the OL lead wire through the harness path as shown in the manual.
  3. Protect the area first remove putty, the terminal cover and any plastic parts that could burn, and place a protective sheet or steel plate so the brazing flame cannot reach nearby parts.
  4. Heat the brazed compressor piping joints and disconnect them. Keep the pipe-cutting angle within the 45 degree slit range shown.
  5. Remove the 2 nuts that secure the compressor.

Applies to: DX6VS / DZ6VS heat pump outdoor units, 3.5 to 5.0 ton

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EA, p. 120. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.