Daikin · Heat pump troubleshooting
Refrigeration repair practice
What is going on
Recover refrigerant before applying heat. Keep the system clean and dry during repair, and always finish with a new liquid line drier, evacuation and charge.
Likely causes
- Contamination from open system
- Moisture entry during repair
Check in this order
- Recover refrigerant in the proper manner before applying any heat.
- Never open a system that is under vacuum. Plug or cap all openings immediately.
- Remove burrs and clean brazing surfaces with sand cloth or paper.
- Clean the inside of new tubing to remove oil and chips.
- Sweep the tubing with dry nitrogen while brazing to prevent oxides.
- Use heat shields and wet rags to protect stop valves, EEV and filters.
- Replace the liquid line drier, then evacuate and charge.
Applies to: Refrigerant circuit repairs on outdoor unit, EEV air handler and cased coil
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin DX6VS/DZ6VS service instructions SiUS612209EB, p. 22. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.