Refrigerant system repair practice (S-100)

DX6VSDZ6VS

What is going on

Remove the refrigerant before applying heat. There is no pump-down function, so recover all refrigerant through the two service ports on the stop valves.

Likely causes

  • Leak or component repair needed on the refrigerant circuit

Check in this order

  1. Recover all refrigerant using the two service ports on the stop valves before applying heat or relocating the unit.
  2. Never open a system under vacuum.
  3. Plug or cap all openings as soon as they are made.
  4. Remove burrs and clean the brazing surfaces with sand cloth or paper.
  5. Clean the inside of new tubing to remove oils and chips.
  6. Sweep the tubing with dry nitrogen when brazing to prevent oxides.
  7. After any repair, replace the liquid line drier, evacuate and charge.
  8. Use a heat shield and wet rags to protect the serial plate, stop valves, EEV and filters.

Applies to: Outdoor units and refrigerant circuit

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin SiUS612209EA service instructions, p. 22. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.