Refrigerant system repair practice (S-100)
What is going on
Remove the refrigerant before applying heat. There is no pump-down function, so recover all refrigerant through the two service ports on the stop valves.
Likely causes
- Leak or component repair needed on the refrigerant circuit
Check in this order
- Recover all refrigerant using the two service ports on the stop valves before applying heat or relocating the unit.
- Never open a system under vacuum.
- Plug or cap all openings as soon as they are made.
- Remove burrs and clean the brazing surfaces with sand cloth or paper.
- Clean the inside of new tubing to remove oils and chips.
- Sweep the tubing with dry nitrogen when brazing to prevent oxides.
- After any repair, replace the liquid line drier, evacuate and charge.
- Use a heat shield and wet rags to protect the serial plate, stop valves, EEV and filters.
Applies to: Outdoor units and refrigerant circuit
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Daikin SiUS612209EA service instructions, p. 22. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.