Daikin · Heat pump troubleshooting

Refrigerant system and discharge thermistor check (Check 14)

FTXM-W/V

What is going on

Checks for refrigerant loss and that the discharge pipe thermistor is seated in its holder.

Likely causes

  • Refrigerant leak or shortage
  • Discharge pipe thermistor came off its holder

Check in this order

  1. Check the refrigerant system for leakage.
  2. If there is a leak or shortage, follow the refrigerant shortage diagnosis (U0).
  3. Check whether the discharge pipe thermistor has come off its holder.
  4. If it is off the holder, reattach it.
  5. Replace the refrigerant if the system check requires it.

Applies to: Refrigerant circuit and discharge pipe thermistor

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin Inverter Pair FTXM-W/V service manual SiUS042113EA, p. 150. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.