Refrigerant removal, purging and recovery on flammable systems

D5FSFA

What is going on

Sequence for breaking into the refrigerant circuit on a flammable refrigerant unit, and for decommissioning.

Check in this order

  1. Isolate the system electrically before starting.
  2. Remove the refrigerant safely under local and national rules. Recover it into correct recovery cylinders if venting is not allowed.
  3. Evacuate the circuit.
  4. Purge the circuit with oxygen-free nitrogen. Do not use compressed air or oxygen.
  5. Break the vacuum with oxygen-free nitrogen, fill to working pressure, vent to atmosphere, then pull a vacuum again. Repeat until no refrigerant remains.
  6. Vent the system to atmospheric pressure before opening the circuit.
  7. Use only recovery cylinders labeled for that refrigerant, and do not fill them above 80% liquid volume.
  8. Do not charge recovered refrigerant into another system unless it has been cleaned and checked.
  9. When decommissioning, label the equipment as emptied of refrigerant, dated and signed, and label it as containing flammable refrigerant.

Applies to: D5FSFAH floor console ductless heat pump

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: D5FSFAH service manual, p. 6-7. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.