Refrigerant removal, purging and recovery on flammable systems
What is going on
Sequence for breaking into the refrigerant circuit on a flammable refrigerant unit, and for decommissioning.
Check in this order
- Isolate the system electrically before starting.
- Remove the refrigerant safely under local and national rules. Recover it into correct recovery cylinders if venting is not allowed.
- Evacuate the circuit.
- Purge the circuit with oxygen-free nitrogen. Do not use compressed air or oxygen.
- Break the vacuum with oxygen-free nitrogen, fill to working pressure, vent to atmosphere, then pull a vacuum again. Repeat until no refrigerant remains.
- Vent the system to atmospheric pressure before opening the circuit.
- Use only recovery cylinders labeled for that refrigerant, and do not fill them above 80% liquid volume.
- Do not charge recovered refrigerant into another system unless it has been cleaned and checked.
- When decommissioning, label the equipment as emptied of refrigerant, dated and signed, and label it as containing flammable refrigerant.
Applies to: D5FSFAH floor console ductless heat pump
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: D5FSFAH service manual, p. 6-7. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.