Carrier · Heat pump troubleshooting

Recovering refrigerant and decommissioning

D5FUAA

What is going on

Recovery and decommissioning steps for flammable refrigerant units.

Check in this order

  1. Confirm the technician knows the equipment and that electrical power is available.
  2. Isolate the system electrically.
  3. Pump down the system if possible; otherwise use a manifold to recover from several points.
  4. Place the recovery cylinder on scales before recovery.
  5. Do not fill cylinders above 80% liquid volume or exceed their maximum working pressure.
  6. Label the equipment as decommissioned and emptied, with date and signature, and mark it as containing flammable refrigerant.
  7. Do not reuse recovered refrigerant unless it has been cleaned and checked.

Applies to: Refrigerant recovery

More heat pump guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: D5FUAA Service Manual, p. 7. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.