Carrier · Heat pump troubleshooting
Recovering refrigerant and decommissioning
What is going on
Recovery and decommissioning steps for flammable refrigerant units.
Check in this order
- Confirm the technician knows the equipment and that electrical power is available.
- Isolate the system electrically.
- Pump down the system if possible; otherwise use a manifold to recover from several points.
- Place the recovery cylinder on scales before recovery.
- Do not fill cylinders above 80% liquid volume or exceed their maximum working pressure.
- Label the equipment as decommissioned and emptied, with date and signature, and mark it as containing flammable refrigerant.
- Do not reuse recovered refrigerant unless it has been cleaned and checked.
Applies to: Refrigerant recovery
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: D5FUAA Service Manual, p. 7. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.