Carrier · Heat pump troubleshooting
Preparing and flaring refrigerant pipe
What is going on
Cut, deburr and flare each pipe end before connecting to the units.
Likely causes
- Burrs or an uneven cut can cause leaks at the flare.
- A deformed or dented pipe loses heating efficiency.
Check in this order
- Measure the distance between the indoor and outdoor units.
- Cut the pipe a little longer than that distance, square at 90°. Do not dent or deform it.
- Remove all burrs with a reamer or deburring tool, holding the pipe pointing down.
- Seal the pipe ends with PVC tape while preparing them.
- Sheathe the pipe in insulation.
- Slide the factory flare nut on the correct way round before flaring. It cannot be turned after flaring.
- Remove the tape, clamp the flare block so the pipe end sticks out past the form, and flare with the tool to the Table 9 dimensions.
- Remove the tool and block, and check the flare for cracks and an even surface.
Applies to: Field copper refrigerant piping
More heat pump guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Carrier D5CURA installation manual, p. 13. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.